The waste water treatment plant in Nemetin, Croatia has been expanded
AAT designed and delivered the gas line consisting of: gravel filter, gas cooling, gas warming, active carbon filter for the reduction of siloxanes and hydrogen sulphides as well as pressure boosters, a double-membrane-gas storage the emergency flare and agitators. This increases the service life of the CHP units for power generation and the operation reliability of the plant.
Design data:
- Gas cooling and warming
Quantity: 200 Nm³/h
- Active carbon filter:
Quantity: 2x 200 Nm³/h
Gas purification of the hydrogen sulphides to < 5 ppm H2S and siloxanes to < 2,0 mg/m³
- Double membrane gas storage:
Nominal volume: 1.530 m³
- Gas emergency flare:
Quantity: max. 250 m³/h
AAT Abwasser- und Abfalltechnik GmbH
Konrad Doppelmayr Straße 17
6960 Wolfurt
Austria
Tel.: +43/5574/65190-0
Fax.: +43/5574/65190-99